- Information
- AI Chat
Was this document helpful?
Power system (11) - NOTES10
Course: Power Electronics (203122357)
21 Documents
Students shared 21 documents in this course
University: Parul University
Was this document helpful?
of go.The value of go is directly proportional to air density. Thus the breakdown strength of air at
a barometric pressure of b cm of mercury and temperature of tºC becomes δg0 where
δ = air density factor =
t
273
92.3
Under standard conditions, the value of δ = 1.
Critical disruptive voltage,
r
d
rgVcln
0
Correction must also be made for the surface condition of the conductor. This is accounted for
by multiplying the above expression by irregularity factor mo.
Critical disruptive voltage,
r
d
rmgVcln
00
kV/phase
where
mo = 1 for polished conductors
= 0·98 to 0·92 for dirty conductors
= 0·87 to 0·8 for stranded conductors
(ii) Visual critical voltage
It is the minimum phase-neutral voltage at which corona glow appears all along the line
conductors.
It has been seen that in case of parallel conductors, the corona glow does not begin at the
disruptive voltage Vc but at a higher voltage Vv, called visual critical voltage. The phase-
neutral effective value of visual critical voltage is given by the following empirical formula
r
d
r
rgmV vv ln)
3.0
1(
0
kV/phase
where mv is another irregularity factor having a value of 1·0 for polished conductors and 0·72 to
0·82 for rough conductors.
(iii) Power loss due to corona Formation of corona is always accompanied by energy
loss which is dissipated in the form of light, heat, sound and chemical action. When
disruptive voltage is exceeded, the power loss due to corona is given by:
2
525
10241 c
VV
d
rf
P
kw/km/phase